1500kV 56kJ Multi-Stage Impulse Voltage Generator

Mar 26, 2022

I.The Scope

The generator is suitable for the test of the air gap insulator string, casing, power transformers and transformer standard lightning impulse voltage full wave, standard operating wave and chopped wave impulse voltage test.

II.The General Conditions of Use

itude: Less than or equal to 1000m

Ambient temperature: -5 degree plus 40 degree

Relative humidity: <>

Maximum daily temperature difference: 25 degree

Use of the environment: indoor

 Non-conductive dust

No fire or explosion hazard

There is no gas that corrodes metal and insulates

Supply voltage waveform is the actual sine wave, waveform distortion rate <>

III.Follow The Standard

GB/T 311.1 Insulation and coordination of

high voltage transmission and conversion equipment

GB/T 16927.1 High voltage test Technology Part I General test requirements

GB/T 16927.2 High voltage test technology Part II Measurement System

GB/T 16896.1 High voltage shock test with digital recorder

JB/T 7616 High-voltage line insulator shock resistance test

DL/T 557 High-voltage line insulator steep wave impact test, definition, test method and criterion

ZBF 24001  Implementation details of impact voltage test

IV.The Nominal Parameter Values

1. Nominal voltage: ±1500kV

2. Rated voltage: ±150kV

3,Nominal energy:56 kJ

4,impact the total capacitance: 0.05mF (1.0mF /75 kV single pulse capacitor, a total of 20)

5,Series: level 10

6. Standard waveform parameters:

⑴Standard lightning impulse voltage full wave, wave head time: 1.2us±30 percent ms,wave end time: 50ms±20 percent   

(2) Truncation wave: Truncation time (2-6)±10 percent s, zero-crossing coefficient Less than or equal to 0.3 percent

(3) Standard operating impulse voltage wave 25020 percent s /250060 percent s,

(4) Steep wave: >1000KV/uS <1500kv>

Voltage utilization factor>85 percent (more than 90 percent when no-load 300PF);

(5) Standard cut-off: cut-off time 2-6S, zero-crossing coefficient ≤ 0.3%, voltage utilization coefficient > 85 percent

The impulse voltage waveform parameters and their deviations meet the requirements of relevant national GB311 and GB16927 standards.

7. The minimum output voltage is greater than 10 percent of the nominal voltage

8. Duration of use: Above 70 percent of the rated voltage, it can be continuously operated by charging and discharging every 120 seconds, and below 70 percent of the rated voltage, it can be continuously operated by charging and discharging once every 60 seconds.

V.Technical Description of Main Components

1. DC Charging Part

(1)Constant current charging device is adopted;

(2)using oil-immersed insulating case charging transformer, the secondary voltage is 80kV , rated capacity 5 KVA;Primary is 220V.

(3)Using 2DL-200 kV /200 mA high voltage rectifier silicon stack,The reverse withstand voltage³200kV, the average current ³ 0.5A, the high-voltage rectifier silicon pile is installed next to the charging transformer, the charging voltage polarity can be reversed automatically by the transmission mechanism. There are polarity switch buttons on the console.

(4)High-voltage rectifier silicon stack protection resistance using enameled resistance wire is tightly wound around the insulation tube;

(5) It adopts bilateral symmetrical constant current charging mode;

(6) During automatic control, the constant current charging device is within the range of 10 percent to 100 percent of the rated charging voltage, the deviation between the actual charging voltage and the set voltage is not more than ±1 percent , the instability of the charging voltage is not more than ±1 percent , and the charging voltage is not more than ±1 percent . The adjustable accuracy is 1 percent ;

(7) 2 DC resistance voltage dividers, using 75kV, 200M, oil-immersed metal film resistors. The low-voltage arm resistors are installed in the bottom flange of the voltage divider, and the voltage signals on the low-voltage arms are introduced into the console with shielded cables;

(8) The automatic grounding switch adopts the electromagnet to open and close the grounding mechanism. When the test stops, the main capacitor can be automatically short-circuited and grounded through the protection resistor;

(9) Inductors, capacitors, charging transformers (including high-voltage rectifier silicon stacks and polarity switching devices) and their protective resistors for constant current charging, automatic grounding switches and insulating pillars are installed on a chassis;

2. The Ontology Part

(1) The main structure adopts a four-column structure. The steel bracket composed of 4 flanges is connected with two capacitors in parallel to form a stable structure. Level stacking, easy disassembly and inspection, and stable overall structure;

(2) The body adopts asymmetrical constant current charging method, thyristor constant current voltage regulation, continuously adjustable from zero to set voltage, the charging power supply is automatically turned off at the moment of ignition and discharge, and the rated voltage of each stage is 150kV;

(3) 10-level tower structure of the main body insulation pillar. Each level includes 2 MWF75-1.0 iron shell oil-immersed pulse capacitors, charging resistance, wave head resistance, wave tail resistance and ignition ball gap, etc.

All synchronous discharge balls are installed in a closed insulation, with a transparent window at the ball gap, and the ball gap can be automatically adjusted through the console with clean air for drying;

(4) A single pulse capacitor is 10.05F, the DC working voltage is 75kV, the capacitor inductance is 0.2H, and the composite film is oil-immersed in insulation. Under the normal working state and working environment of the capacitor, the capacitor outlet bushing can withstand a vertical pulling force of 15kg, while ensuring that No damage and oil leakage;

(5) The wave head (front) resistance and wave tail resistance are all of plate-shaped structure, non-inductive winding, and their self-inductance is 2.5H (the purpose of reducing the inductance is to increase the load capacity, for extra-large-capacity loads (such as greater than 5000PF) This item can use a suitable combination of external modulating capacitors and modulating resistors to achieve the purpose of increasing the load.), the joints are all spring crimping type;

(6) The wave head (front) and wave tail resistor brackets can be connected in parallel by four resistors at the same time. The wave head (front) and wave tail resistors have the same length and can be used in common use. The position of the short-circuit rod; it is convenient to make the generator run in series with the short-circuit rod;

(7) Complete with

7.1 4 sets of lightning wave head resistors;

7.2 3 sets of wave tail resistors;

7.3 1 set of charging resistor (1 spare);

7.4 2 wave modulating capacitors

(8) The first-stage ball gap adopts bilateral opposite polarity triggering, and the second-stage to tenth-stage ball gap adopts three-gap ball gap ignition, and the synchronization error rate or rejection rate is not more than 2 percent ; .

(9) The distance between the ball gaps at all levels is adjusted linearly by the motor, the control system indicates the charging voltage corresponding to the ball distance, and the transmission structure has upper and lower limit switches;

(10) The ball gap distance can be adjusted manually or automatically on the control system;

(11) The body can be used in parallel with each stage or multiple stages, and the parallel connecting rod adopts a unified connector, which is convenient for connection. The redundant wave modulating resistance can be placed on the equipment without affecting the electrical performance;

(12) The body is equipped with an insulating ladder, and its load capacity is designed to be 120kg, so as to facilitate the staff to replace the wave modulation element, and the brackets for the wave modulation resistor and the connecting rod are stored in each stage of the test;

(13) The bottom level of the body adopts a solid insulating column, and the other levels use two-end sealed insulating cylinders, which have good sealing performance;

(14) Anti-corona measures are taken between all levels, and there will be no obvious corona during the whole charging process.

(15) Equipped with a safety grounding system, it is convenient for the test personnel to climb the body to replace the resistance or start the grounding system during maintenance, and all capacitors are short-circuited and grounded.

(17) Interstage insulation and mechanical support can withstand 165kV DC voltage without discharge.

(18) The climbing insulating ladder installed on the body is convenient to work, safe and reliable, and the body machinery can fully meet the mechanical and electrical strength.

(19) The top of the generator is equipped with a pressure equalizing cover, which is composed of tortoise block aluminum sheets.

3. ±1500KV Weak Damping Capacitor Divider

The high voltage arm capacitor consists of 2 sections, each section has a rated parameter of 750kV/600 pF, and the rated lightning impulse withstand voltage is 1500kV.

The voltage divider is equipped with a low voltage arm capacitor, the voltage dividing ratio is 3000, and the voltage dividing ratio accuracy is less than ±1 percent ;

The square wave response characteristics of the weakly damped capacitive voltage divider meet the requirements of GB311 standard

4. 900kV Multi-stage Truncation Gap Device

Including six 1800 pF/150kV equalizing capacitors, six pairs of chopper ignition ball gaps, 2-5s delay trigger device, etc. The interception time is 2 to 6s, the standard deviation of the dispersion of the interception time is not more than 0.1s, and the distance of the multi-ball interception ball gap is adjusted by the console through the electric transmission mechanism.

5. 600KV steepening device

The device includes: a steepening ball gap and its electric transmission device, the steepening ball gap adopts a flat spherical shape, and the distance between the ball gaps can be adjusted electrically.Capacitive voltage divider for steepening capacitors, steepening ball gap, electric drive mounted on the same chassis.

6. 600KV Line Insulator Steep Wave Resistive Divider

600kV fast steep wave resistance divider, the resistance of the high voltage arm is about 2.5 kΩ, and the resistance of the low voltage arm is about 1.2 Ω. The rated working voltage is 600 kV, the voltage divider ratio error is not more than 2 percent , the partial square wave response time is not more than 10 nanoseconds, the stabilization time is not more than 100 nanoseconds, overshoot: Less than or equal to 20 percent , measurement uncertainty: Less than or equal to ±1 percent , measuring steep wave <1000kv>